Dry Contacts

The UPS provides input dry contacts and output dry contacts.
2.3.1

Input Dry Contacts

There are several input dry contacts at the X3 slot.
Figure 8
Input dry contacts
Table 1
Input dry contacts at X3
Position
Name
J4.1
ENV
J4.2
BtG
J4.3
GEN
J4.4
+12V
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
J28
J4
J26 J30 J10
EPO
Dry in
MBC
X2
X3
Description
3
Battery Room Alarm (N.C.)
Battery Ground Fault Detection (N.C.)
1,2
Generator Join Detection (N.O.)
+12V Power