Cable Lengths: Floor To Connection Point Inside Ups; Table 35 Maintenance Bypass Cabinet Dimensions; Table 36 Multi-Module Paralleling Cabinet Dimensions; Table 37 Distance To Connection Points On The Nx Ups - Emerson Liebert NX 10-30kVA Installation Manual

Liebert nx series 10-30kva, 208v, 60hz
Table of Contents

Advertisement

Table 35
Maintenance bypass cabinet dimensions
Unit
Width
inch
27.2
mm
690
Table 36
Multi-module paralleling cabinet dimensions
1+1 Cabinet Type
1+N Narrow
Types A00, BR0, CR1, DR1
1+N Cabinet Type
1+N Narrow
Types A00, E00, J00
1+N Wide
All other types
8.2

Cable Lengths: Floor to Connection Point Inside UPS

To help calculate the total cable length required, refer to Table 37 for the distance from the floor to
selected connection points inside the NX. Determine the cable length required to reach the NX, then
add the appropriate length from the table and adequate slack for repair and maintenance.
Table 37
Distance to connection points on the NX UPS
Connection Point on UPS
Bypass AC input supply
UPS output AC
Neutral busbars—Input and Output
Battery power
Auxiliary cables: Monitor board (U2)
Communications
Ground
Parallel Board
Depth
Height
31.4
63
825
1600
Width
27.2
690
Width
27.2
690
58.5
1488x
Distance
From
Floor
in. (mm)
30 (750)
30 (750)
11 (280)
16 (400)
60 (1500)
55 (1400)
8 (197)
70(1780)
Depth
Height
31.4
63
825
1600
Depth
Height
31.4
63
825
1600
31.4
63
825x
1600
From
Top of Unit
in. (mm)
30 (750)
30 (750)
55 (1397
58 (1474)
20 (508)
25 (635)
56 (14227)
20(508)
70
Specifications and Technical Data