Table 31 Multi-Module Bypass Cabinet Electrical Data - Emerson Liebert NX 10-30kVA Installation Manual

Liebert nx series 10-30kva, 208v, 60hz
Table of Contents

Advertisement

Table 30
Maintenance bypass cabinet electrical data (dual input)
System
Rectifier
I/P Voltage
Max Input
kVA Type
(VAC)
15
F, P
480
15
F, P
600
15
F, P
208
15
F, P
220
15
F, P
240
10
F, P
480
10
F, P
600
10
F, P
208
10
F, P
220
10
F, P
240
Table 31
Multi-module bypass cabinet electrical data
System
Size
Type
kVA
30
20
A00, BR0
15
10
CR1
30
1+1
CR1, DR1
30
CR1, DR1
30
CR1, DR1
30
CR1
20
CR1, DR1
20
CR1, DR1
20
CR1, DR1
20
CR1
15
CR1, DR1
15
CR1, DR1
15
CR1, DR1
15
CR1
10
CR1, DR1
10
CR1, DR1
10
CR1, DR1
10
Rectifier
Bypass
Input OCP
Max Input
Current
CB Size (A)
Current
21
30
17
30
49
60
46
60
42
60
14
20
12
15
33
40
31
40
29
40
System
System
I/P Voltage
Max Input
(VAC)
Current
208
104
208
70
208
53
208
35
208
107
220
101
480
46
600
37
208
71
220
68
480
31
600
25
208
54
220
51
480
23
600
19
208
36
220
34
480
16
600
12
Bypass
Input OCP
O/P Voltage
CB Size (A)
(VAC)
24
30
208
19
20
208
54
60
208
51
60
208
47
50
208
16
20
208
13
15
208
36
40
208
34
40
208
32
40
208
System
Input OCP
O/P Voltage
CB Size (A)
(VAC)
125
208
90
208
70
208
45
208
150A
208
150A
208
70A
208
60A
208
100A
208
100A
208
50A
208
40A
208
80A
208
80A
208
40A
208
30A
208
60A
208
50A
208
30A
208
20A
208
62
Specifications and Technical Data
Nominal O/P
Output OCP
Current Rating (A)
CB Size (A)
42
42
42
42
42
28
28
28
28
28
Nominal O/P
Output OCP
Current Rating (A)
CB Size (A)
83
56
42
28
83
83
83
83
56
56
56
56
42
42
42
42
28
28
28
28
60
60
60
60
60
40
40
40
40
40
125
70
60
40
125
125
125
125
70
70
70
70
60
60
60
60
40
40
40
40