Table E-2: Operating and Performance Specifications for Power Enclosures
(North America/Japan)
Item
Output voltage
specifications
Rated output voltage
Rated output current
Rated output power
Nominal power
Ambient temperature
1
range
Operating
Shipping
Relative humidity, noncondensing
Operating
Non-operating
Wet bulb temperature
Operating
Non-operating
1
Operating temperature has an altitude derating of 1°C (33.8°F) per 304.8 m (1,000 ft). No direct
sunlight. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit
is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude
maximum for storage is 70 KPa.
E-4
continued
Single-Phase Model
-48.8 VDC to -54 VDC
99 A
4,298 W
4,158 W at 208 VAC
10° to 35°C
(50° to 95°F)
-30° to 60°C
(-22° to 140°F)
2
20% to 80%
5% to 95%
28°C
(82.4°F)
38.7°C
(101.7°F)
HP ProLiant BL p-Class System Setup and Installation Guide
Three-Phase Model
-48.8 VDC to -54 VDC
170 A
8,310 W
7,202 W at 208 VAC
10° to 35°C
(50° to 95°F)
-30° to 60°C
(-22° to 140°F)
20% to 80%
5% to 95%
28°C
(82.4°F)
38.7°C
(101.7°F)