2000 Series | Program Entry Guide | 4.0

4.0 Receiver

4.1

Modem Reports

1 Rcvr Format
Default:
Modem
Modem, Pulse
Selection:
0
Pulse
1
Modem
Rcvr Format
Set
to Modem to transmit reports in Modem II format with its advanced reporting capabilities.
You need firmware revision 8.00 or greater installed in your D6500 Receiver.
Table 2 shows the reports available.
The D6500 line card ack tone table must contain "Modem II for D9112." Refer to the 6500: Line Program Entry
Guide.
Rcvr Format
Set
to Pulse to transmit in 4x2 Pulse Format. Be sure to program codes for each report group. Refer
to the Section 4.2 Pulse Report Groups.

Table 2: Modem II Reports Chart

Modem II Report
AC FAILURE
AC RESTORE
ALARM REPORT POINT
001 (-099)
ALARM REPORT
RECENT CLOSING
ID=001
POINT=001(24)
ALARM CROSS POINT
001 (-099)
BATTERY LOW
BATTERY MISSING
BATTERY RESTORE
CANCEL REPORT
CANCEL REPORT
ID
001 (-008)
Bosch Security Systems | 7/05 | 35114F
Receiver
Description
No AC power to system. Control panel runs on battery.
AC Power is restored to normal.
Alarm Report from Points 1 to 24 or from an A, B, C, key. Refer to Section 7.0 ABC Keys for
instructions on setting reports from the keys.
If an alarm occurs within 2 minutes of a Closing event, the system sends an Alarm Recent
Close Report.
Alarm Report from Points 1 to 24 with point code for Cross or Partner point.
The ALARM RECENT CLOSE message overrides the ALARM CROSS POINT message.
The ALARM EXIT ERROR message does not apply to Cross, Partner, Double Knock, or Alarm
Verification points
System battery is low.
System battery is disconnected. Battery must be missing for 60 seconds.
Missing or low battery is restored.
Cancel Report from keyswitch.
Cancel Report with user ID for users 1 to 8.
EN | 15