5.14 N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
This configuration has not been reviewed by UL.
Figure 32: N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
To Serial Connection
See 485 interface
connection note
N-485-PCI-2
485 -
NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A
DIP Switch Settings
S1:ON
S2:ON
S3:ON
S4:ON
S5:ON
S6:ON
S7:ON
S8:OFF
1
NetAXS TB7
X
Shield
485
Common
485 +
485 Interface ConnectionTypes
RS-485
N-485-PCI-2
N-485-HUB-2
N-485-PCI-2L
Ground Shield
DO NOT CONNECT or
GROUND SHIELD
2
3
DIP Switch Settings
DIP Switch Settings
S1-S5:Panel Address
S1-S5:Panel Address
S6: OFF
S6: OFF
J36: CLOSED
J36: OPEN
J37: CLOSED
J37: OPEN
Ground only one
side of cable shield
4,000 ft.(1,200 m) max,24 AWG,2 twisted pairs with
shield,120 ohm,23 pf (HAS part no.NCP2441-TN)
NetAXS™ NX4L1 Installation
System Configuration
NetAXS Panel
COM Port
M-56K Modem
LANSRL100 or LANSRLU1
X
1
2
3
NetAXS TB7
45