4.5 Supervised Input Wiring
The supervised inputs are located on TB4 and TB13
through Input 8 may be configured for normally open or normally closed contacts as
supervised or non-supervised. Inputs 13 and 14 are on TB8. All eight inputs have
default functions, but they can be configured for general purpose inputs.
The following table identifies the default function for each terminal position.
Table 3 Default Supervised Input Assignments
Terminal Position
TB4-1
TB4-3
TB4-4
TB4-6
TB8-1
TB8-3
TB13-1
TB13-3
TB13-4
TB13-6
TB 5-6, 6-6, 11-6,
12-6
NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A
Default Function
Door 1 REX (Egress)
Door 1 Status
Door 2 REX (Egress)
Door 2 Status
External Power Supply AC FAIL
Panel Tamper
Door 3 REX (Egress)
Door 3 Status
Door 4 REX (Egress)
Door 4 Status
Optional supervised input if not used
for a reader tamper
NetAXS™ NX4L1 Installation
Installation
(Figure 8
on page 18). Input 1
17