Reader Wiring; Table 1 Cabinet Electrical Entries; Table 2 Reader Wiring - Honeywell NETAXS NX4L1 Installation Manual

Access control unit
Hide thumbs Also See for NETAXS NX4L1:
Table of Contents

Advertisement

NetAXS™ NX4L1 Installation
Installation
Table 1

Table 1 Cabinet Electrical Entries

ENCLOSURE
Top
Bottom
Right Side
Left Side
Back

4.4 Reader Wiring

Each reader port supports a single 12-volt reader with Wiegand output format. Power
to the readers is shared with the AUX Power ports TB3 and TB14. The maximum
power draw is 600 mA for readers and AUX Power combined.
To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is
required. If the optional reader buzzer feature is not needed, you can use the standard
six-conductor cable (HAS part number NC1861-BL). The cable shield should be
grounded at the panel only. Grounding at both ends can cause ground loops which can
be disruptive. The maximum recommended length of wiring is 500 feet per reader.

Table 2 Reader Wiring

TB5-1, 6-1, 11-1, 12-1
TB5-2 6-2, 11-2, 12-2
TB5-3, 6-3, 11-3, 12-3
TB5-4, 6-4, 11-4, 12-4
TB5-5, 6-5, 11-5, 12-5
TB5-6, 6-6, 11-6, 12-6
TB5-7, 6-7, 11-7, 12-7
16
www.honeywell.com
lists the dimensions of the cabinet's conduit entries.
CONDUIT
1/2" (12.7 mm)
5
2
8
6
N/A
Terminal
Wire Color
Brown
Green
White
Black
Red
Variable
Variable
CONDUIT
CONDUIT 1"
3/4" (19.0 mm)
(25.4 mm)
5
N/A
2
N/A
8
N/A
6
N/A
N/A
Wiegand Reader
LED Control
Wiegand Data 0
or Data
Wiegand Data 1
or Clock
Common
12VDC Power
Tamper
Buzzer
CONDUIT 2"
(50.8 mm)
2
2
N/A
N/A
2
N/A