4.0 Installation

Perform the following steps to install the NX4L1 panel:
Warning:
1. Review the panel layout, cable runs, and power needs.
2. Mount the enclosure at the proper location on the wall. Use appropriate
3. Run all I/O wires to the enclosure, and properly mark each wire for its use.
4. Run appropriate length three-wire cable to the enclosure power inlet terminal
5. Remove each terminal plug one at a time to wire the properly labeled cables.
6. Connect the shield to the grounding studs.
7. Set DIP switch settings for the panel address (see
8. Check all wiring at this time.
result in a loss of warranty.
9. Apply power to the panel. The power-up sequence may take up to two minutes,
10.Configure the panel by following the instructions in the NetAXS™ Access
NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A
Use a static strap whenever touching the panel to ensure protection from
Electrostatic Discharge (ESD).
anchors for the mounting material.
block. Ensure that the ground wire is properly grounded to earth. Note that an
Optional Power Connection kit (HAS part number 100-00049) is available for
the NX4L1 panel. To install the Power Connection option, see
Optional AC
Inlet" on page 10 for instructions. The power inlet terminal block
can accommodate wire sizes up to 12 AWG. Wiring to a 20-amp branch circuit
requires 12 AWG insulated copper wire. Wiring to a 15-amp branch circuit
requires 14 AWG insulated copper wire. Connect the line, neutral, and earth
ground wires to the appropriate terminal on the power inlet terminal block.
Do not apply power at this time.
Caution:
See the wiring diagram
length to secure to the grounding stud. Also, maintain a distance of at least .25
inches between the non-power limited wiring (115 VAC/60 Hz input wiring,
power line filter wiring, 24 VDC wiring, battery backup/charger wiring, and
battery-to-battery wiring) and all other wiring, which is power-limited Class 2
wiring.
Do not apply power at this time.
Caution:
J36 and J37 for communication termination and biasing (see
Configuration" on page 31 and
Improper wiring can cause damage to the NetAXS™ at power up and
Caution:
after which the RUN LED blinks green. The RUN LED is located near
Terminal Block (TB) 8. After the power-up sequence, check the LEDs to be
sure the panel has powered up properly (see
Control Unit User's Guide.
(Figure 35
on page 52). Leave enough shield drain
"Jumper
Settings" on page 28).
"LED
NetAXS™ NX4L1 Installation
Installation
"Installing the
Table 5
on page 27), and set
"System
Operation" on page 47).