DC Power Cables

Figure 1-7 shows the power cable and connector. Table 1-3, "Power Cable Pinouts," identifies the pinouts on
the connector.
Figure 1-7
Table 1-3
J1
Description
Shield GND
A1
-48 VDC (A)
A2
RTN (A)
A3
-48 VDC (B)
A4
RTN (B)
Case
Shield GND
1
ALARM SET
2
PS WARN CL
3
RMT PWR OFF CL
4
VINA FLT CL
5
VINB FLT CL
6
PS FLT CL

Connecting DC Power to High-Availability Systems

For complete power redundancy in high-availability systems, connect each power supply to
NOTE
Chapter 1
DC Power Cables
A1
Power Cable Pinouts
J1
10
11
1
A2
9
A3 A4
AWG
2
MM
12
3.31
12
3.31
12
3.31
12
3.31
22
.326
22
.326
22
.326
22
.326
22
.326
22
.326
Connecting the Server to DC Power Source
Part Number Z7535-63002
Color
Black
White
Red
Green
Black
White
Red
Green
Orange
Blue
Installation