Cable Strain Relief; Safety Grounding - HP L1000 - 9000 - 0 MB RAM Manual

Carrier grade addendum - rp5400 series of servers
Hide thumbs Also See for L1000 - 9000 - 0 MB RAM:
Table of Contents

Advertisement

Cable Strain Relief

Figure 1-4 shows the power cables are secured to the bottom of the side tray with the cable tie wraps and
attached to the front of the tray.
Figure 1-4
Figure 1-5 shows the power cables are secured at the back of the tray by a strain relief bar. When
connecting the power cables to the power source, ensure that there is enough slack in the cables to fully
extend the tray.
Figure 1-5

Safety Grounding

The rp5400 Series of Server Carrier Grade System has a grounding lug on the rear panel for connecting to
earth ground. The server must be connected to earth ground using a minimum 6 AWG (16mm
suitable Listed/Certified terminal such as Thomas and Betts part number 54205.
Chapter 1
Cable Installation
Cable Strain Relief
Connecting the Server to DC Power Source
Strain Relief Sleeve
Installation
Strain Relief Bar
2
) wire with a