Mounting the ACE3600 Frame on a Wall

WARNING:
Before drilling holes for mounting the frame, make sure there are no
electrical wires installed inside the wall at the holes' location.
CAUTION:
If the ACE3600 is subject to high levels of shock or vibration, you
must take suitable measures to reduce the acceleration or amplitude.
We recommend that you install the ACE3600 on vibration-damping
materials (for example, rubber-metal anti-vibration mountings).
Wall Mount Installation
For convenient installation of the ACE3600 RTU on a wall, allow an additional 6 cm
(2.4") (in W, H) and 7 cm (2.75") (in D) around the plate. Four holes are provided, one in
each corner of the RTU metal chassis, for wall mounting the RTU. The figures below
show the dimensions (in mm) of the various frames/metal chassis and the distances
between the holes.
Small Metal Chassis
Small/Large Metal Chassis Installation Dimensions and Screw Holes for Installation
295 mm
88
ACE3600 Installation Guidelines
410 mm
Large Metal Chassis