In the event of AI Module failure, the I/O module ERR LED will be lit. The event is
registered by the CPU in the Error Logger. AI Module failure status is also visible to the
user application program.
In addition to the ERR LED, the module includes an Underflow (UDF) and Overflow
(OVF) LED for each input.
When the UDF LED is lit, it indicates that the signal level in the corresponding
input is below the nominal range.
When the OVF LED is lit, this indicates that the signal level in the corresponding
input is above the nominal range.
If both the UDF and OVF LEDs of the same channel are lit, the channel is
uncalibrated.
The AI module can be diagnosed and monitored using the STS Hardware Test utility.
The Hardware Test verifies that the module is operational, presents the module
configuration and shows the actual value of each input, including overflow and
underflow. It is also possible to change the input filter setup for the duration of the
Hardware Test.
In the Hardware Test utility, it is possible to set the AI module to Freeze Mode. In this
mode, the program user will get the KLV or PDV of each input in the module instead of
the actual input value. Freeze mode enables testing the inputs while the user application
program is running.