Weight
120/230V 16DI Module
Total Number of Inputs
Input Characteristics
Input Arrangement
AC Input Frequency
AC Input Change Delay
Max. DC Input Voltage
DC Input Pulse Width
"ON" DC Voltage Range
"OFF" DC Voltage Range
"ON" AC Voltage Range
"OFF" AC Voltage Range
Input Current
Permitted Voltage Difference
Between Groups
Input Filtering
Diagnostic LEDs
User Connection
Cable and TB Holder
Module Replacement
Input Isolation
Input Insulation
Operating Voltage
Power Consumption
Dimensions
Weight
Specifications subject to change without notice.
16 DI: approx. 0.28 Kg (0.62 lb)
32 DI: approx. 0.29 Kg (0.63 lb)
16 DI
IEC 61131-2 Type 1
Two isolated groups of 6 inputs and one isolated group of 4
inputs.
47 – 63 Hz
Maximum 25.0 msec
Max. ±264 V DC (relative to input common)
Minimum 7.0 msec @ 230 V DC
+79.0 V DC to +264.0 V DC, -79.0 V DC to -264.0 V DC
-40 to +40 V DC
79 to 264 V AC (RMS)
0 to 40 V AC (RMS)
At 110V DC
1.0 to 3.0 mA
At 230V DC
0.4 to 2.0 mA
At 110V AC
> 2.0 mA RMS
At 230V AC
> 3.0 mA RMS
2.5 kV RMS
0 to 50.8 msec (DC, programmable in 0.2 msec steps)
Note: Minimum effective filter value is 7.0 msec.
Status LED per each input, module error LED
3 Terminal Blocks (5.00mm pitch), Maximum 14 AWG
30 Wire Cable with TB Holder connector, 20 AWG wires
Hot swap replacement – module extraction/insertion under
voltage
2.5 kV RMS between input and module logic per IEC60255-5
Insulation resistance 100 MΩ @ 500 V DC
10.8-16 V DC and 3.3 V DC ±10% (from the motherboard
connector)
Refer to Appendix C: ACE3600 Maximum Power Ratings.
37 mm W x 225 mm H x 180 mm D, (1.5" W x 8.7" H x 7.1" D)
approx. 0.367 kg (0.80 lbs)