Each DI can be set in the Application Programmer I/O link table to trigger recording of
time tagged events upon any input change of state. The time tagged events are recorded
in the CPU memory and can be retrieved for various purposes.
Each input can be configured to KLV or to a PDV (0, 1) in the Application Programmer
I/O link table. This value is shown to the user application program in the event of DI
module failure. Also, the predefined value can be used during normal operation to force a
value that masks the actual input value. In this case the user application program will get
the PDV instead of the actual input value.
Each output can be configured to "Keep Last Value" KLV or to a "Predefined Value"
PDV (0, 1). This value is executed when the user application program stops or when the
module has no communication with the CPU module.
Also, the predefined value can be used during normal operation to force a value on the
output by ignoring the user application program value.
The DO/DI FET module features which can be configured are listed in the table below.
Some parameters are per module and some are per input.
Parameter
Selection
DI Fast Capture
Disabled /Enabled
*
DI Filter
0-254 (x 0.2 mS)
*
DI Counter Filter
0-255 (x 0.05 mS)
DI Event Time
Disabled /Enabled
Tagging
DI Keep Last
KLV/PDV
Value &
PDV = 0/1
Predefined Value
DI Mask
No /Yes
DO Keep Last
KLV/PDV
Value &
PDV = 0/1
Predefined Value
*
The counters are limited to 1Khz; therefore filtering is relevant from 1mS and above. In this module the
minimum relevant value for DI Filter is 5 and the minimum value for DI Counter Filter is 20.
Digital Output and Digital Input FET Modules
Default
Per Module/
Setup
Input
Disabled
Input
50 (10 mS)
Module
20 (1 ms)
Module
Disabled
Input
KLV
Input
No
Input
KLV
Output
46
Parameter Setup
Location
RTU configuration
RTU configuration;
'C' Program
RTU configuration;
'C' Program
Application
Programmer I/O link
table
Application
Programmer I/O link
table
Application
Programmer I/O link
table
Application
Programmer I/O link
table