Power checkout

Power problems can be difficult to solve. For example, a short circuit can exist
anywhere on any of the power distribution buses. Usually, a short circuit will cause
the power subsystem to shut down because of an overcurrent condition.
A general procedure for troubleshooting power problems is as follows:
1. Turn off the server, and disconnect all ac power cords.
2. Check for loose cables in the power subsystem. Also check for short circuits, for
3. Remove adapters and disconnect the cables and power connectors to all
4. Reconnect all ac power cords and turn on the server. If the server starts
To use this method, you must know the minimum configuration that is required for
the server to start (see page 97).
28
326m Type 7969: Hardware Maintenance Manual and Troubleshooting Guide
example, if there is a loose screw causing a short circuit on a circuit board.
internal and external devices until the server is at the minimum configuration
required to start the server (see "Minimum operating requirements" on page 97).
successfully, replace adapters and devices one at a time until the problem is
isolated. If the server does not start from the minimal configuration, replace
FRUs of minimal configuration one at a time until the problem is isolated.