Commissioning
13.4.6 To perform a test run on the gas boiler
Installer reference guide
194
2 Select test program " ". See
4
boiler" [
194]. Static pressure MUST be 20 mbar (+ or – 1 mbar). If the
working pressure is <19 mbar, the gas boiler output will be reduced and the
correct combustion reading may NOT be obtained. Do NOT adjust the air and/
or gas ratio. To obtain sufficient working pressure, gas supply MUST be
correct.
INFORMATION
Make sure the working inlet pressure does NOT interfere with other gas appliances
installed.
The gas boiler has a test run function. Activating this function results in the
activation of the gas boiler (pump starts and fan starts with a fixed speed), without
the control functions being actuated. The safety functions remain active. The test
run can be stopped by pressing
after 10 minutes. To perform a test run, switch off the system with the user
interface.
Make sure that the leaving water temperature home page, room temperature
home page, and domestic hot water home page are turned OFF.
There may be no error on the gas boiler or the heat pump module. During a gas
boiler test run, "busy" will be displayed on the user interface.
Program
Burner ON at minimum
power
Burner ON, maximum
space heating power
setting
Burner ON, maximum
domestic hot water
setting
Stop test program
"13.4.6 To perform a test run on the gas
and
simultaneously or will end automatically
Button combination
and
and (1×)
and (2×)
and
Display
Actual situation
EJHA04AAV3 + EHY2KOMB28+32AA
Daikin Altherma H Hybrid
4P531180-1D – 2025.03