3.2.4 Brine
3.2.5 Water
EJHA04AAV3 + EHY2KOMB28+32AA
Daikin Altherma H Hybrid
4P531180-1D – 2025.03
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
If applicable. See the installation manual or installer reference guide of your
application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area
immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room,
e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply with the safety and
environmental precautions specified in the applicable legislation.
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure water quality complies with EU directive 2020/2184.
Avoid damages caused by deposits and corrosion. To prevent corrosion products
and deposits, observe the applicable regulations of technology.
Measures for desalination, softening or hardness stabilization are necessary if the
filling and top-up water have a high total hardness (>3 mmol/l–sum of the calcium
and magnesium concentrations, calculated as calcium carbonate).
Using filling water and top-up water which does NOT meet the stated quality
requirements can cause a considerably reduced service life of the equipment. The
responsibility for this is entirely that of the user.
3
General safety precautions
|
Installer reference guide
15
Need help?