EJHA04AAV3 + EHY2KOMB28+32AA
Daikin Altherma H Hybrid
4P531180-1D – 2025.03
If the LED is flashing, the controller has detected a problem. Once the problem is
rectified, the controller can be restarted by pressing the
Following table shows a list of error codes and the possible solutions.
Error code Cause
10, 11, 12,
Sensor fault S1
13, 14
20, 21, 22,
Sensor fault S2
23, 24
0
Sensor fault after self-
check
1
Temperature too high
2
S1 and S2 interchanged
4
No flame signal
5
Poor flame signal
6
Flame detection fault
8
Incorrect fan speed
29, 30
Gas valve relay fault
16
button.
Possible solution
▪
Check wiring
▪
Replace S1
▪
Check wiring
▪
Replace S2
Replace S1 and/or S2
▪
Air in installation
▪
Pump is NOT running
▪
Insufficient flow in installation
▪
Radiators are closed
▪
Pump setting is too low
▪
Check cable set
▪
Replace S1 and S2
▪
Gas tap is closed
▪
No or incorrect ignition gap
▪
Gas supply pressure is too low or fails
▪
Gas valve or ignition unit is NOT powered
▪
Condensate drain blocked
▪
Check adjustment of gas valve
▪
Replace ignition cable and spark plug cap
▪
Replace ignition unit
▪
Replace boiler controller
▪
Fan catching on casing
▪
Wiring between fan and casing
▪
Check wiring for poor wire contact
▪
Replace fan
Replace boiler controller
Troubleshooting
|
Installer reference guide
219