If the LED is flashing, the controller has detected a problem. Once the problem is
rectified, the controller can be restarted by pressing the
Following table shows a list of error codes and the possible solutions.
Error code Cause
10, 11, 12,
Sensor fault S1
13, 14
20, 21, 22,
Sensor fault S2
23, 24
0
Sensor fault after self-
check
1
Temperature too high
2
S1 and S2 interchanged
4
No flame signal
5
Poor flame signal
6
Flame detection fault
8
Incorrect fan speed
29, 30
Gas valve relay fault
16
button.
Possible solution
Check wiring
Replace S1
Check wiring
Replace S2
Replace S1 and/or S2
Air in installation
Pump is NOT running
Insufficient flow in installation
Radiators are closed
Pump setting is too low
Check cable set
Replace S1 and S2
Gas tap is closed
No or incorrect ignition gap
Gas supply pressure is too low or fails
Gas valve or ignition unit is NOT powered
Condensate drain blocked
Check adjustment of gas valve
Replace ignition cable and spark plug cap
Replace ignition unit
Replace boiler controller
Fan catching on casing
Wiring between fan and casing
Check wiring for poor wire contact
Replace fan
Replace boiler controller
Troubleshooting
|
Installer reference guide
219