Wired controller - SAVA X
EN
OPERATION
13. ROTATION & BACK-UP INDICATION (some models)
When there are two units, press the button to select the rotating function, and press
"Conrm"to turn on or o the rotating function.
1. Step 1: press "Conrm" to set the rotating time,then press the button "^" or "v" to set
time. Setting time Range: 1~99h,the default time is 10 hours.
2. Step 2: set high temperature co-open temperature -- or 26~32 degrees -- that is,
this function is invalid. When the ambient temperature is 26~32 degrees, when
the ambient temperature is greater than or equal to the set temperature, the two
machines will run 24 degrees at the same time in the COOL mode.
3. Step 3: set the low-temperature co-open temperature -- or 5-15 degrees -- that is,
this function is invalid. When the ambient temperature is 5-15 degrees, when the
ambient temperature is lower than the set temperature, the two units will run at the
same time for 24 degrees to make the heating mode.
4. Step 4: set which machine will run rst. Select A or B.
5. After this function is turned on, as long as the air conditioner is running at the setting
hour, it will automatically turn on another air conditioner and turn o the current air
conditioner. Press the POWER button to switch to another one immediately. A or
B icons icker to indicate the corresponding air conditioning failure. Automatically
switch to another machine when running time is reached or machine failure occurs.