The iBoot-PDU4-N20 and iBoot-PDU8-N20
provide a linecord for connection to a 20 Amp
115VAC service. The total maximum current load
for all outlets on these models cannot exceed 20
Amps, 16 Amps sustained load.
The iBoot‐PDU8‐2N20 provides two linecords for
connection to 20 Amp 115VAC services. The total
maximum current load for outlets on any linecord
cannot exceed 16 Amps. Each linecord distributes
power to four outlets.
The iBoot-PDU4-C10 and iBoot-PDU8-C10 are
for international applications and can be used on
100V to 240VAC. These models provide an IEC
320 style universal inlet for connecting a
detachable power cord. A standard IEC to CEE7
European cord set is supplied with the unit for use
on 10 Amp 240VAC service*. The total maximum
current load for all outlets cannot exceed 12 Amps
at 115VAC or 10 Amps when used at 240VAC.
The iBoot-PDU8-2C10 is for international
applications and can be used on 100V to 240VAC.
The iBoot-PDU8-2C10 provides two IEC 320 style
universal inlets for connecting a detachable power
cord. Two standard IEC to CEE7 European cord
sets are supplied with the unit for use on 10 Amp
240VAC service*. The total maximum current load
for outlets on any linecord cannot exceed 12 Amps
at 115VAC or 10 Amps when used at 240VAC.
Each linecord distributes power to four outlets.
The iBoot-PDU4-C20 and iBoot-PDU8-C20 is
for international applications and can be used on
100V to 240VAC. The iBB-C20 provides an IEC
320 C20 style universal inlet for connecting a
detachable power cord. A standard IEC to CEE7
European cord set is supplied with the unit for use
on 20 Amp 240VAC service*. The total maximum
current load for all outlets cannot exceed 16 Amps.
The iBoot-PDU8-2C20 is for international
applications and can be used on 100V to 240VAC.
The iBoot-PDU8-2C20 provides two IEC 320 C20
style universal inlets for connecting a detachable
power cord. Two standard IEC to CEE7 European
cord sets are supplied with the unit for use on 16
Amp 240VAC service*. The total maximum current
load for outlets on any linecord cannot exceed 16
Amps. Each linecord distributes power to four
outlets.
* Power cords for other countries are available from your local source. If a power cord with a different
terminating plug is required, be sure it is properly rated and meets all the required local electrical