Sideflow Clean Pro
5.7. Fault contact SFC
The Sideflow Clean Pro can forward faults to the building management system.
The active fault message can be forwarded to the building management system by a
direct connection to terminal A6 (NO) and terminal A6 – C.
During normal operation without fault message, contact A6–C and contact A6–NO are
closed, contact A6-C to A6-NC is open.
In case of an active fault message or an interrupted
Power supply, contact A6-C and contact A6–NO are opened and contact A6–C is
closed with contact A6–NC.