Danfoss iC7 Series Operating Manual page 28

Air-cooled and liquid-cooled system modules
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

Operating Guide | iC7 Series Functional Safety
2.
In MyDrive® Insight, go to Device > Setup & Service > Software update.
3.
To update software, select the file to be updated in the drive.
4.
If relevant, select Allow devices to restart to allow the devices to restart after the update is finished. This selection is optional.
5.
Check the installed version, available version, and status.
6.
Click Update.
7.
Check the alert message and click Yes/No.
8.
Click Done to acknowledge and finish the update.
9.
Verify that the software update has been successful.
a.
Go to Device info > Extended device information and verify the firmware version.
b.
Run the commissioning test.
A commissioning test is required after each modification of the installation of an application that involves safety
functions. For more information, see
What to do next:
For more information, see the MyDrive® Insight documentation.
Troubleshooting the software update
1.
Restart the device.
2.
Check that the device is in normal state and there are no errors.
3.
Check the software package version and compatibility, and retry the software update.
If the problem persists and the device stays in error mode, contact Danfoss.
28
| Danfoss Drives Oy © 2024.09
7.2 Commissioning
Test.
Configuration Tools
AQ477043679710en-000102 / 172K2965A