Operating Guide | iC7 Series Functional Safety
iC7 Functional Safety
3
Functional Safety Options
3.1
Functional safety option +BEF2 includes Safe Torque Off (STO) and Safe Stop 1 time-controlled (SS1-t) safety functions. Drives with +BEF2
also include an advanced safety unit, which enables configuring functional safety parameters using MyDrive® Insight.
Functional Safety System Description
3.2
An additional advanced safety unit is used to implement safety functions in accordance with the standard EN IEC 61800-5-2 in iC7 system
modules with +BEF2.
The advanced safety unit handles the safe I/O and the monitoring of active safety functions. The advanced safety unit does not handle
the controls of the AC drive. The AC drive can be controlled, for example, with the drive application, or the external process control
system.
The advanced safety unit can be controlled with the digital I/Os and over safe fieldbus, where applicable.
Figure
1 describes the system architecture of drives with the functional safety units.
Danfoss Drives Oy © 2024.09
iC7 Functional Safety
AQ477043679710en-000102 / 172K2965A |
11
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?