Operating Guide | iC7 Series Functional Safety

MyDrive Insight

6.4
Installing MyDrive® Insight
6.4.1
1.
To install the tool, go to https://suite.mydrive.danfoss.com/content/tools.
2.
Install MyDrive® Insight.
For more information on how to use the tool, see the online help in MyDrive® Insight.
3.
Use MyDrive® Insight to connect the drive to a PC.

Backing up and Restoring Parameters

6.4.2
The parameter backup and restore functionality in MyDrive® Insight can be used to back up and restore all or part of the drive
parameters.
1.
Log into MyDrive® Insight® as admin.
2.
Go to Device > Setup & Service > Parameters > Live.
3.
Click Create backup/Restore on the menu bar.
What to do next:
For more information, see the MyDrive® Insight documentation.

Performing a Factory Reset

6.4.3
The factory reset can be performed separately for each parameter group, or for all settings.
1.
In MyDrive® Insight, go to Device > Setup & Service > Restore > Select Restore Content.
To reset all settings, select All Settings.
To reset only the functional safety settings, select Functional Safety Configuration Variables.
Ü
After performing a factory reset, all parameters are in a Not commissioned state and their values are restored to default values.
A factory reset also resets the user name and password to their defaults. Parameters must be configured again or alternatively,
restored from a backup.
After performing a factory reset, all parameters have to be checked and set again.
Parameters for safety functions that are not used must also be checked. For example, parameters must also be checked for
l
SS1 functions, even if only STO function is used and vice versa.

Updating Software

6.4.4
Prerequisite:
The drive must not be running during the update process.
l
Updating software related to functional safety requires logging into MyDrive® Insight with the default admin account in the
l
drive.
Do not power down or restart the devices during a software update. Creating a backup of the current parameters before updating any
software is highly recommended, in case parameters need to be restored after the software update is completed. For instructions, see
6.4.2 Backing up and Restoring
1.
Log into MyDrive® Insight as admin.
Danfoss Drives Oy © 2024.09
Parameters.
  NOTICE
  NOTICE
Configuration Tools