Technical Data
Input Characteristics
Model No.
Mains voltage
Stand-by power
Switched power
Warming-up
Safety and EMC
EMC standard (EMC)
Safety standard (LVD)
Radio Equipment (RED)
Certi cation
Intelligent
Photocell
Mechanical Structures and Installations
For more details, please refer to user manual.
A. Ceiling mount (HIM34A)
Subject to change without notice.
HIM34
220~240VAC 50/60Hz
<1W
Max. 20pcs devices, 40mA
30s
EN55015, EN61000-3-2/-3-3
EN60669-1/-2-1,
AS/NZS60669-1/-2-1
EN300440, EN301489-1-3,
EN62479
CE , UKCA
Ambient daylight
One-Key
Rotary Switch
threshold
Commissioning
Programing
LED indicator
Daylight sensor
PIR
Sensor module
Installation rack
TM
Sensor Data
Model No.
Sensor principle
Operation frequency
Transmission power
Sensor mode
Detection area (Max.)*
Detection range
Detection angle
Environment
Operation temperature
IP rating
Detection Pattern
0
9
15
Infrared receiver
Rotary switch for programing
Cable entry
Edition: 25 Mar. 2024
IP65
HIM34
High Frequency (microwave), PIR
5.8GHz +/- 75MHz (HF)
<0.2mW (HF)
PIR, HF, PIR+HF, PIR/HF
Max installation height:
15m (forklift)/12m (human)
Max detection range:
HF: Ø = 24m (forklift)/14m (human)
PIR: Ø = 24m (forklift)/20m (human)
10% / 50% / 75% / 100%
360
O
O
O
Ta: -20
C ~ +50
C
IP65
Ver. A0
Page 1/6

Advertisement

loading
Need help?

Need help?

Do you have a question about the HIM34 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hytronik HIM34

  • Page 1 IP65 High Bay Dual Sense Sensor HIM34 IP65 HF and PIR, Daylight Harvest for Independent DALI Technical Data Sensor Data Input Characteristics Model No. Model No. HIM34 HIM34 Sensor principle High Frequency (microwave), PIR Mains voltage 220~240VAC 50/60Hz Stand-by power Operation frequency <1W...
  • Page 2 B. Screw to the Luminaire by conduit (HIM34B) 59.6 0.825” Infrared receiver LED indicator Rotary switch for programing Photocell 66.6 89.9 Sensor module Cable entry C. Attach to the shade by clamp (HIM34C) Infrared receiver LED indicator Rotary switch for programing Photocell Angle adjustment 28.5...
  • Page 3: Wiring Diagram

    Driver Black DALI + DALI HIM34 1. 200 metres (total) max. for 1mm〔 CSA (Ta = 50メ) 2. 300 metres (total) max. for 1.5mm〔 CSA (Ta = 50メ) Detection Pattern End user can choose the suitable PIR lens in real application to ful ll various requirements. Three options are offered for selection:...
  • Page 4: Functions And Features

    Functions and Features Daylight Harvest Light will not switch on The light switches on The light turns on at full or dims to maintain the lux level. The light output when natural light is automatically with regulates accroding to the level of natural light available. suf cient, even there is presence when natural motion detected.
  • Page 5 Settings (Remote Control HRC-11) Press button “ON/OFF” to select permanent ON or permanent OFF mode. * Press button “AUTO”/ “RESET” to exit this mode. Press button “RESET”, perform DIP Switch/Rotary Switch settings. *The default settings are: Detection range 100%; Hold-time 5min; Stand-by time +∞; threshold Stand-by dimming level 10%;...
  • Page 6 Additional Information / Documents 1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation 2. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy Subject to change without notice.

This manual is also suitable for:

Him34bHim34cHim34aHim34-a-l1