Stand-alone Dual Sense Motion Sensor

HIM17
HF and PIR, trailing edge sensor with tri-level control
Mechanical Structure
C - Surface box
B - Facia Cover
PIR
Infrared receiver
Photocell
HF Sensor module
A - Control Board
Installation:
For more details, please refer to user manual.
Direct junction "J" box mounting
1
Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors
from false-triggering.

Technical Data

Input Characteristics
Model No.
Mains voltage
Stand-by power
Load ratings:
Trailing edge driver
100W@120V; 150W@220 -277V
Resistive
120W@120V; 200W@220 -277V
Warming-up
Safety and EMC
EMC standard (EMC)
Safety standard (LVD)
Radio Equipment (RED)
Certi cation
Semko, CB, CE , EMC, RED, RCM
Subject to change without notice.
LED indicator
Sensor mode selection
HIM17
120~277VAC 50/60Hz
<1W
30s
EN55015, EN61000
EN60669, AS/NZS60669
EN300440, EN301489-1,
EN62479
TM
56
Note: the blinds are optional, they may be inserted
behind the lens for focussing the detection range.
Surface mount assembly
2
Sensor Data
Model No.
Sensor principle
Operation frequency
Transmission power
Sensor mode
Detection angle
Environment
Operation temperature
IP rating
Edition: 26 Feb. 2020
A
Blind
B
Blind
HIM17
High Frequency (microwave), PIR
5.8GHz +/- 75MHz (HF)
<0.2mW (HF)
4 modes: PIR, HF, PIR+HF, PIR/HF
Max. ( O x H) 12m x 6m
360
O
Ta: -20
O
C ~ +55
IP20
RED
Ver. A0
O
C
IP20
Page 1/6

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Dual Sense HIM17 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hytronik Dual Sense HIM17

  • Page 1 Stand-alone Dual Sense Motion Sensor HIM17 HF and PIR, trailing edge sensor with tri-level control Mechanical Structure C - Surface box B - Facia Cover Infrared receiver Photocell HF Sensor module LED indicator Blind Sensor mode selection Rotary switch preset Blind A - Control Board Note: the blinds are optional, they may be inserted...
  • Page 2 Dual Sense Introduction It’s commonly known Microwave and Infrared are main detecting technologies in lighting controls. Both have the advantage and disadvantage for industrial applications. Advantage Advantage * sensitive to minor motion. * no penetration, con ned detection area. * sensitive to radial movement. * sensitive to tangential movement.
  • Page 3 Tri-level Control (Corridor Function) Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insuf cient) -->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period;...
  • Page 4 Settings (Remote Control HRC-11) Permanent ON/OFF function Press button “ON/OFF” to select permanent ON or permanent OFF mode. * Press button “AUTO”, “RESET” to quit this mode. The mode will change to AUTO Mode after power failure. Reset Settings Press button “RESET”, all settings go back to rotary switch settings. Sensor detection mode returns to DIP switch settings.
  • Page 5 Daylight threshold Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable. Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button rst. Ambient daylight threshold 1.
  • Page 6 Additional Information / Documents 1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation 2. Regarding precautions for PIR sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors - Precautions for Product Installation and Operation...

This manual is also suitable for:

Him17

Table of Contents