4 | Compressor assembly
INFO
4.1 Storage and transport
?
4.2 Setting up
D
GB
ATTENTION Attachments (e.g. pipe holders, additional units, fastening parts,
F
E
10 | AQ451925859810en-000301
New compressors are factory-filled with inert gas. Leave this
service charge in the compressor for as long as possible and
prevent the ingress of air. Check the compressor for transport
damage before starting any work.
Storage at (-30°C) - (+70°C), maximum permissible relative humidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet.
Do not lift manually!
Use lifting gear!
etc.) directly to the compressor are not permissible!
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Sun protection: If the compressor is set up outdoors, it has
to be protected from direct sunlight.
© Danfoss | Climate Solutions | 2024.07