3| Areas of application
Maximum admissible frequency: 60 Hz
Maximum admissible operating pressure (LP/HP)
19/28 barg (276/406 psig)
4| Compressor assembly
4.1
Storage and transport
?
4.2
Setting up
© Danfoss | Climate Solutions | 2024.04
New compressors are factory-filled with inert gas. Leave this
service charge in the compressor for as long as possible and pre-
vent the ingress of air. Check the compressor for transport damage
before starting any work.
Storage at -30°C...+70°C (-22°F...+158°F), maximum permissible
relative humidity 10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Installation of pipe vibration mufflers is recommended!
1)
:
LP = Low pressure
1)
HP = High pressure
AQ450438640296en-US0301 | 9
US
Need help?
Do you have a question about the BOCK UL-HGX66e and is the answer not in the manual?
Questions and answers