New compressors are factory-filled with inert gas. Leave this
service charge in the compressor for as long as possible and pre-
vent the ingress of air. Check the compressor for transport damage
before starting any work.
Storage at -30°C...+70°C (-22°F...+158°F), maximum permissible
relative humidity 10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!
1
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Sun protection: If the compressor is set up outdoors, it has
to be protected from direct sunlight.
F
E
D
C
AQ450440479309en-US0201 | 9
US

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BOCK UL-HGX12P and is the answer not in the manual?

This manual is also suitable for:

Bock ul-hgx12p/60 s 0,7Bock ul-hgx12p/75 ml 1Bock ul-hgx12p/75 s 2Bock ul-hgx12p/90 ml 2Bock ul-hgx12p/90 s 2Bock ul-hgx12p/110 ml 2 ... Show all

Table of Contents