Download Print this page

Eu-Konformitätserklärung; Eu Declaration Of Conformity - Bender ISOMETER iso 1685D-25 Series Quick Start Manual

Insulation monitoring device

Advertisement

Zul. Fremdgleichspannung U
fg
Zul. Fremdgleichspannung U
fg
Zulässige Netzableitkapazität C
..................................................profil- und geräteabhängig, 0...2000 μF
Schnittstellen
Schnittstelle/Protokoll ..................................... RS-485/BMS/Modbus RTU
Messkreis für Isolationsfehlersuche [isoxx1685DP]
Prüfstrom I
DC ............................................................................ ≤ 50 mA
L
Prüftakt/Pause ................................................................................ 2 s/4 s
Schaltglieder
Schaltglieder 3 Wechsler:
K1 .................................................................... (Isolationsfehler, Alarm 1)
K2 .................................................................... (Isolationsfehler, Alarm 2)
K3 ....................................................................................... (Gerätefehler)
Kontaktdaten nach IEC 60947-5-1
Bemessungsisolationsspannung ......................................................250 V
Minimale Kontaktbelastbarkeit ............................ 1 mA bei AC/DC ≥10 V
Sonstiges
EMV .................................................................................... IEC 61326-2-4
Schutzart Einbauten (DIN EN 60529) ..................................................IP30
Schutzart Klemmen (DIN EN 60529) ...................................................IP30
EU-Konformitätserklärung
Link zum vollständigen Text der EU-Konformi-
tätserklärung ist über den QR-Code verfügbar:
UKCA-Konformitätserklärung
Der vollständige Text der UKCA-Konformitäts-
erklärung ist über den QR-Code verfügbar:
Bender GmbH & Co. KG
Londorfer Straße 65
35305 Grünberg
Germany
Tel.: +49 6401 807-0
info@bender.de
www.bender.de
[isoHV1685D] ........................≤ DC 3150 V
[isoLR1685DP] ........................≤ DC 720 V
................................................................
e
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung nur mit
Genehmigung des Herausgebers.
All rights reserved.
Reprinting and duplicating only with
permission of the publisher.
Permissible extr. DC voltage U
Permissible extr. DC voltage U
Permissible system leakage capacitance C
...............................................profile and device dependent, 0...2000 μF
Interfaces
Interface/protocol ............................................ RS-485/BMS/Modbus RTU
Measuring circuit for ins. fault location [isoxx1685DP]
Locating current I
DC .................................................................. ≤ 50 mA
L
Test cycle/Pause .............................................................................. 2 s/4 s
Switching elements
Switching elements 3 changeover contacts:
K1 .....................................................................(insulation fault, Alarm 1)
K2 .....................................................................(insulation fault, Alarm 2)
K3 ........................................................................................ (device error)
Contact data acc. to IEC 60947-5-1
Rated insulation voltage ..................................................................250 V
Minimum contact rating ........................................ 1 mA at AC/DC ≥ 10 V
Other
EMC ..................................................................................... IEC 61326-2-4
Degree of protection, built-in components (DIN EN 60529) ............... IP30
Degree of protection, terminals (DIN EN 60529) ................................ IP20

EU Declaration of Conformity

The full text of the EU Declaration of Conformity
is available via the QR Code:
UKCA Declaration of Conformity
The full text of the UK declaration of conformity
is available via the QR Code:
© Bender GmbH & Co. KG, Germany
Subject to change! The specified
standards take into account the edition
valid until 02/2024 unless otherwise
indicated.
[isoHV1685D] .......................≤ DC 3150 V
fg
[isoLR1685DP]........................≤ DC 720 V
fg
................................................
e

Advertisement

loading
Need help?

Need help?

Do you have a question about the ISOMETER iso 1685D-25 Series and is the answer not in the manual?

This manual is also suitable for:

Iso1685dp-425Isohv1685d-425Isolr1685dp-325B91065802B91065805B91065803