Wiring Power Supply And Ground - Omron Z5FP-MC10 Setup Manual

Multi-dimensional sensor
Table of Contents

Advertisement

Wiring Power Supply and Ground

Wire the power supply and the ground to their respective terminals. Tighten the screws using a torque
between 0.5 and 0.6 N⋅m. After wiring, confirm that the wiring is correct.
Reinstall the terminal block protection covers after wiring so that the terminal blocks are covered.
Crimp Terminals and Cables
The terminal block uses M3 terminal screws.
Use appropriate crimp terminals for M3 screws as shown below.
Recommended Model
Forked
6.2mm max.
Round
6.2mm max.
Ground Wiring
Always connect a ground wire to the ground terminal of the Controller independently of other
devices. To avoid grounding problems, do not share the ground wire with any other devices or
wire the ground to the building's steel framing.
Use a grounding point that is as close as possible and keep the ground wiring as short as
possible.
Ground to 100
or less.
Manufacturer
J.S.T. Mfg Co., Ltd.
V1.25-N3A
J.S.T. Mfg Co., Ltd.
V1.25-MS3
SECTION 1
Wiring and Connection
Recommended wire
Model
size
1.31 to 1.65 mm
2
19
Setup Manual

Advertisement

Table of Contents
loading

Table of Contents