DeviceNet Wireless Master Station Specifications

DeviceNet setting switch
(SW1)
Wireless setting switch
(SW3)
WCH switch
Set the communication speed and status of the DeviceNet interface here.
Set the switches before turning on the power supply. Only the setting values
detected immediately after the power supply has been turned on are enabled.
Changes to switch settings after the power supply has been turned on are
ignored.
SW1
ON
1 2
3 4
No.
Contents
1
Communication
(MODE1)
speed selection
2
(MODE2)
3
Status/No status
4
Maximum number of I/O points
• DeviceNet communication speed settings
Communication
speed (bps)
MODE1
125k
OFF
250k
ON
500k
OFF
-
ON
No.
Contents
3
Status/No status
4
Maximum number of
I/O points
Perform the various settings for TEST and SET modes. Set the switches
before turning on the power supply. Only the setting values detected immedi-
ately after the power supply has been turned on are enabled.
Changes to switch settings after the power supply has been turned on are
ignored.
SW3
ON
1 2
3 4
5
7 8
6
No.
Contents
1
(Usually OFF)
2
(Usually OFF)
3
Wireless channel monitor
4
Installation test
5
Confirmation test
6
Wireless slave station entry
7
Wireless slave station deletion
8
Default configuration
Set the frequencies for the wireless interface group addresses. The settings
should be made in decimals in a range from 01 to 34 will result in a switch set-
ting error. For normal operation modes, settings outside of the valid range will
DIP switch status
1
2
MODE2
OFF
OFF
ON
ON
ON
Status
1,600/1,600 points
(100 words/100 words)
ON
-
-
Performed
Performed
Performed
Entries
Deletes
Default settings
used
Section 4-1
Remarks
Length of main line: 500m
Length of main line: 250m
Length of main line: 100m
Settings prohibited, no
communication
OFF
No status
512/512 points
(32 words/32 words)
OFF
-
-
Not performed
Not performed
Not performed
Does not entry
Does not delete
Default settings not
used