Setting Selectors and Switch

2-3-3 FUNCTION Switch

FUNCTION
Baud Rate (Serial
Communications)
Baud rate
19,200 bps
Pin 1
Pin 2
Memory Bank Designation
Method
E5ZD-SDL Setting Display
Unit Connection
The FUNCTION switch is used to set the parameters of the E5ZE, such as the
baud rate and startup operation.
Set the baud rate using pins 1 and 2 to the baud rate of the host device con-
nected to the EZ5E.
9,600 bps
The factory setting is 9,600 bps (pin 1 ON, pin 2 OFF).
Pin 3 is used to set the memory bank designation method.
Memory bank
designation
Pin 3
The factory setting is for communications (pin 3 OFF).
When contact inputs are used to switch memory banks, the specified memory
bank will be used for all control points.
Pin 4 is used to specify when an E5ZD-SDL Setting Display Unit is connected.
E5ZD-SDL connection
Pin 4
The factory setting is for no connection (pin 4 OFF). Set pin 4 to ON when an
E5ZD-SDL Setting Display Unit is to be connected to the E5ZE.
Operation mode change
Not used. (Always set to OFF.)
Temperature unit (°C or °F)
Startup operation
E5ZD-SDL Setting Display Unit connection
Memory bank designation method
Baud rate (serial communications)
4,800 bps
Communications
Not connected
Section
2-3
2,400 bps
Contact inputs
Connected
13