Omron E5ZE Operation Manual page 67

Multipoint temperature controller
Hide thumbs Also See for E5ZE:
Table of Contents

Advertisement

Specifications
Item
Dead
–999 to 999°C/°F (in units of 1°C/°F)
band/overlap
band
Upper-limit
ON/OFF pulse type: (Lower-limit output value + 0.1)% to 100.0% (in units of 0.1%)
Linear output type: (Lower-limit output value + 0.1)% to 105.0% (in units of 0.1%)
output value
Lower-limit
ON/OFF pulse type: 0.0% to (Upper-limit output value – 0.1)% (in units of 0.1%)
Linear output type: –5.0% to (Upper-limit output value – 0.1)% (in units of 0.1%)
output value
Output value
0.0% to 100.0% per sampling period (200 ms approx.) in units of 0.1%
change rate
limit
Alarm
Setting unit
output
Alarm
Upper- and
setting
mode
lower-limit
range
(See note 1)
Upper-limit
(See note 1)
Lower-limit
Upper- and
lower-limit
range
Absolute-
value up-
per-limit
(See note 1)
Absolute-
value lower-
limit (See
note 1)
HB and HS
alarm
CT input measurement range
CT input measurement accu-
racy
HB and HS alarm setting range 0.0 to 50.0 A (in units of 0.1 A)
HB and HS alarm setting accu-
racy
HB alarm min. detection ON
time
HS alarm min. detection OFF
time
Fuzzy strength
Fuzzy scale 1
Fuzzy scale 2
Insulation resistance
Dielectric strength
Vibration resistance
62
1
0° to 9,999°C/°F
–999° to 9,999°C/°F
–999° to 9,999°C/°F
0° to 9,999°C/°F
–999° to 9,999°C/°F
–999° to 9,999°C/°F
–999° to 9,999°C/°F
0.0 to 55.0 A AC(in units of 0.1 A)
±5% FS ± 1 digit max. (between 0.0 to 50.0 A)
There is no difference between the CT input measurement accuracy and HB and HS
alarm setting accuracy.
Control output must be continuously ON for 100 ms min.
Control output must be continuously OFF for 100 ms min.
0% to 99% (in units of 1%)
0.2 to 999.9°C/°F (in units of 0.1°C/°F)
0.02 to 99.99°C/s or °F/s (in units of 0.01°C/s or °F/s)
20 MΩ min. between the FG terminal and all input terminals (at 500 VDC)
500 VAC for 1 minute between the FG terminal and all input terminals
Malfunction:
Vibration frequency:
Acceleration:
Direction and time:
Destruction:
Vibration frequency:
Acceleration:
Direction and time:
Specification
0.1 (See note 2)
0.0° to 9,999.9°C/°F
–999.9° to 9,999.9°C/°F
–999.9° to 9,999.9°C/°F
0.0° to 9,999.9°C/°F
–999.9° to 9,999.9°C/°F
–999.9° to 9,999.9°C/°F
–999.9° to 9,999.9°C/°F
10 to 55 Hz
2
15 m/s
8 min each in X, Y, and Z directions
10 to 55 Hz
2
20 m/s
8 min each in X, Y, and Z directions
Appendix A

Advertisement

Table of Contents
loading