Power Supply and Input Wiring

2-5-3 Terminal Arrangement

2-5-4 Power Supply

2-5-5 Ground

18
• Use the crimp terminals shown in the following diagram.
Crimp Terminals
7.9 mm max.
7.9 mm max.
End Soldering
Length of exposed wire: 6 to 8 mm
Applicable wire size: AWG 22 to 16
The following diagram shows the arrangement of terminals on the terminal
block.
Thermocouple
24 VDC
ch 0
Don't use
Don't use
ch 1
Don't use
ch 2
Don't use
Don't use
ch 3
FG
The power supply specifications are as follows:
24 VDC (20.4 to 26.4 VDC) 15 W + 20% max.
Use a power supply with a minimum capacity of 2 A. Be sure to consider the in-
rush current.
Connect the ground wire to terminal 26. Ground to 100 Ω max.
Terminal Block Screw Dimensions
8.1 mm
Platinum Resistance Thermometer
ch 4
ch 0
ch 5
ch 1
Don't use
Don't use
ch 2
ch 6
ch 3
ch 7
FG
Section
2-5
9.5 mm
8 x M3.5 self-rising screws
24 VDC
ch 4
ch 5
Don't use
ch 6
ch 7