FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports
IP Router Table Error
Bit 4
0
No error
1
Error detected (More than 8 records, or invalid IP address).
DNS Server Error
Bit 5
0
No error
1
Error detected. (The setting of the IP address of the DNS server is not correct, or communications with the
DNS server timed out.)
Routing Table Error
Bit 6
0
No error
1
Error detected in routing table check.
Ethernet Advanced Setting Error
Bit 9
0
No error
1
An error was detected during the validity check of vendor-specific parameters for the TCP/IP Interface
Object and Ether Link Object.
BOOTP Server Error
Bit 10
0
No error
1
Error detected. (A time-out occurred during communications with the BOOTP server).
SNTP Server Error
Bit 11
0
No error
1
Error detected. (The setting of the host specification (IP address or host name) of the SNTP server is not
correct, or communications with the SNTP server timed out.)
Address Mismatch
Bit 14
0
No error
1
Error detected. (The address conversion method was set for automatic generation, but the last eight bits of
the local IP address does not match the local node address (FINS node address), or the host section other
than the last byte of the local IP address is non-zero.)
Non-volatile Memory Error
Bit 15
0
No error
1
Error detected. (The non-volatile memory's service life has expired, or the memory has failed).
Total Number of Packets Received (Response)
The total number of packets received by the EtherNet/IP Unit or built-in EtherNet/IP port is returned.
Total Number of Receive Errors (Response)
The total number of packet errors detected while the EtherNet/IP Unit or built-in EtherNet/IP port was receiving
is returned.
The following types of error are detected:
• Short packet errors
• Alignment errors
Meaning