Omron CJ1W-EIP21 - 10-2010 Operation Manual page 108

Ethernet/ip units
Table of Contents

Advertisement

CIO Area Allocations
80
Bit
Name
4
IP Router Table
Error
5
DNS Server Error
6
Routing Table Error ON
7 to 8
(Not used)
9
Ethernet Expan-
sion Settings Error
10
BOOTP Server
Error
11
SNTP Server Error ON
12 to
(Not used)
13
14
Address Mismatch ON
15
Non-volatile Mem-
ory Error
Status Manipulated
by
ON
Unit
ON when the IP router table
information is incorrect.
OFF
Unit
OFF when the IP router table
information is correct.
ON
Unit
One of the following errors
occurred when using the DNS
server.
• An illegal server IP address
is set.
• A communications timeout
occurred with the server.
OFF
Unit
OFF when the IP router table
information is correct.
Unit
ON when the routing table
information is incorrect.
OFF
Unit
OFF when the routing table
information is correct.
---
---
---
ON
Unit
One of the following parame-
ters is invalid.
• FINS settings
OFF
Unit
OFF when the parameters
above are valid.
ON
Unit
One of the following errors
occurred when using the
BOOTP server.
• The IP address received
from the BOOTP server is
incorrect.
• A communications timeout
occurred with the server.
OFF
Unit
OFF when the errors listed
above did not occur.
Unit
One of the following errors
occurred when using the
SNTP server.
• An illegal server IP address
or host name is set.
• A communications timeout
occurred with the server.
OFF
Unit
OFF when the errors listed
above did not occur.
---
---
---
Unit
ON when the target IP
address conversion method is
set to Automatic generation,
but the local IP address' host
ID does not match the FINS
node address.
OFF
Unit
OFF when the values match.
ON
Unit
ON when an error occurred in
the Unit's internal non-volatile
memory.
OFF
Unit
OFF when the Unit's internal
non-volatile memory is oper-
ating normally.
Section 4-2
Unit operation

Advertisement

Table of Contents
loading

Table of Contents