Omron CJ1W-EIP21 - 10-2010 Operation Manual page 388

Ethernet/ip units
Table of Contents

Advertisement

Connection Status Codes and Error Processing
Connection status
General
Additional
Status
Status
(hex)
(hex)
01
0109
Error code returned from target:
The connection size settings
are different in the originator
and target.
01
0110
Error code returned from target:
The target was unable to open
the connection, because of its
operating status, such as down-
loading settings.
01
0111
Error code returned from target:
The RPI was set to a value that
exceeds the specifications.
01
0113
Error code generated by origi-
nator or returned from target:
Attempted to open more con-
nections than allowed by the
specifications (CJ2M-EIP21:
32, other CPU Units: 256).
01
0114
Error code returned from target:
The Vendor ID and Product
Code did not match when open-
ing connection.
01
0115
Error code returned from target:
The Product Type did not match
when opening connection.
01
0116
Error code returned from target:
The Major/Minor Revisions did
not match when opening con-
nection.
01
0117
Error code returned from target:
The tag set specified in the con-
nection's target variables does
not exist.
360
Source of error
Configuration 1
Check the connection sizes set in the originator and target.
Check whether
the tag data link is
stopped at the tar-
get. (Restart the
tag data link com-
munications with
the control bit.)
This error does
not occur.
Check the con-
nection settings
(number of con-
nections) at the
originator and tar-
get.
This error does
not occur.
This error does
not occur.
Check the major
and minor revi-
sions set for the
target device and
connection. If nec-
essary, obtain the
EDS file and set it
again.
Check whether
the originator and
target tag sets
and tags are set
correctly.
CJ2 CPU Units
Only: Check sym-
bol settings in the
CPU Unit.
Handling
Configuration 2
Configuration 3
Depends on the tar-
Check whether the
get's specifications.
tag data link is
(Contact the target
stopped at the origi-
device's manufac-
nator. (Restart the
turer.)
tag data link commu-
nications with the
control bit.)
Check the target's
Set the originator's
RPI setting specifica-
RPI setting to 10
tions.
seconds or less.
Check the connec-
Check the connec-
tion settings (number
tion settings (number
of connections) at
of connections) at
the originator and
the originator and
target.
target.
Check the connec-
Check the connec-
tion specifications for
tion specifications for
another company's
another company's
devices.
devices.
Depends on the tar-
Check the origina-
get's specifications.
tor's connection set-
(Contact the target
tings.
device's manufac-
turer.)
Confirm that the tar-
get device's EDS file
is correct.
Depends on the tar-
Check the origina-
get's specifications.
tor's connection set-
(Contact the target
tings.
device's manufac-
turer.)
Confirm that the tar-
get device's EDS file
is correct.
Depends on the tar-
Check the origina-
get's specifications.
tor's connection set-
(Contact the target
tings.
device's manufac-
turer.)
Confirm that the tar-
get device's EDS file
is correct.
Depends on the tar-
Check the origina-
get's specifications.
tor's connection set-
(Contact the target
tings. Check whether
device's manufac-
the target's tag sets
turer.)
and tags are set cor-
rectly.
CJ2 CPU Units Only:
Check symbol set-
tings in the CPU
Unit.
Section 14-3