CIP Message Communications
Example of Additional Status in case that General Status Is 01 Hex.
(Status of Connection Manager Object)
General Status
Additional
(hex)
Status (hex)
01
0100
01
0103
01
0106
01
0107
01
0108
01
0109
01
0110
01
0111
01
0113
01
0114
01
0115
01
0116
01
0117
01
0118
01
0119
01
011A
01
011B
01
0203
01
0204
01
0205
01
0206
01
0207
01
0301
01
0302
01
0303
01
0304
01
0311
01
0312
01
0315
01
0316
01
0317
01
0318
01
0319
01
031A
01
031B
01
031C
01
031D
01
031F
01
0320-07FF
Connection in Use or Duplicate Forward Open.
Transport Class and Trigger combination not supported
Ownership Conflict
Connection not found at target application.
Invalid Connection Type. Indicates a problem with either the Connection Type or Prior-
ity of the Connection.
Invalid Connection Size
Device not configured
RPI not supported. May also indicate problem with connection time-out multiplier, or
production inhibit time.
Connection Manager cannot support any more connections
Either the Vendor Id or the Product Code in the key segment did not match the device
Product Type in the key segment did not match the device
Major or Minor Revision information in the key segment did not match the device
Invalid Connection Point
Invalid Configuration Format
Connection request fails since there is no controlling connection currently open.
Target Application cannot support any more connections
RPI is smaller than the Production Inhibit Time.
Connection cannot be closed since the connection has timed out
Unconnected Send timed out waiting for a response.
Parameter Error in Unconnected Send Service
Message too large for Unconnected message service
Unconnected acknowledge without reply
No buffer memory available
Network Bandwidth not available for data
No Tag filters available
Not Configured to send real-time data
Port specified in Port Segment Not Available
Link Address specified in Port Segment Not Available
Invalid Segment Type or Segment Value in Path
Path and Connection not equal in close
Either Segment not present or Encoded Value in Network Segment is invalid.
Link Address to Self Invalid
Resources on Secondary Unavailable
Connection already established
Direct connection already established
Miscellaneous
Redundant connection mismatch
No connection resources exist for target path
Vendor specific