Drivers, parameters, diagnostics messages and
address space
A.1

Parameter assignment

Parameter assignment in the user program
You can reconfigure individual channels of the module in RUN without this having an effect on
the other channels.
Changing parameters in RUN
The parameters are transferred to the module with the "WRREC" instruction via data record 128.
Output parameter STATUS of the WRREC
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.
Error_
Error_
Code_1
Code_2
0xB0
0x00
0xB1
0x01
0xB2
0x00 to 0xFF Module cannot be reached
0xE0
0x01
0xE0
0x02
0xE1
0x01
0xE1
0x06
0xE1
0x0E
DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB
Cause
Number of the data record unknown
Length of the data record is incorrect
Wrong version in the header
Header error (number or length of parameter
block)
Reserved bit set
Invalid encoding for substitute value reaction
Invalid redundancy parameter assignment
Remedy
Enter valid number for data record.
Enter valid value for data record length.
Check station - is the module plugged in
correctly?
Check the parameters of the WRREC in‐
struction.
Correct the version number of the parameter
block.
Correct the length and number of the param‐
eter blocks.
Check and correct the parameters
A
31