PROFINET IO

4.1

Parameters/address space

4.1.1

Parameters

The table below shows the parameters for the I/O device
DIQ 16x24VDC/0.5A/2A M12-L 8xM12.
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameters
Diagnostics: Undervoltage 1L+
Diagnostics: Missing 2L+
Diagnostics: Short-circuit
Diagnostics: Wire break detection and
alarm
Input delay
Hardware interrupt on rising edge
Hardware interrupt on falling edge
Digital inputs/outputs DIQ 16x24VDC/0.5A/2A M12-L 8xM12 (6ES7143-6BH00-0BB0)
Equipment Manual, 02/2022, A5E46571210-AC
Value range
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Disable
Enable
Disable
Enable
Default
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
Disable
Channel
Disable
Channels 4...7, 12...15
Disable
Channel
Disable
Channel
(Digital inputs)
3.2 ms
Channel
(Digital inputs)
Disable
Channel
(Digital inputs)
Disable
Channel
(Digital inputs)