Emergency Operation; Feo; Feo - Interruption Of Power; Feo Phase I And Battery Lowering Device - Smartrise C4-H Installation And Testing Procedure

Table of Contents

Advertisement

..C4-H Testing
Procedures..
5. To revert back to normal operation, reconnect the SFM and/or SFP relays.

10 Emergency Operation

10.1 FEO

The following sections describe Fire Fighters' Emergency Operation (FEO) test procedures.
10.1.1 FEO – Interruption of Power
Applicable Code – ASME A17.1/B44-19 sections 2.27.3.4
The following procedure describes how to test for interruption of power.
1. Recall the car using Fire Phase I.
2. Verify by running the car on Fire Phase II operation.
3. Reset the main line power.
4. Reset FEO using lobby key switch.

10.1.2 FEO Phase I and Battery Lowering Device

Applicable Code – A17.1/B44-19 section 2.27.3.1.6(m)
The following procedure describes how to test FEO Phase I and Battery Lowering Device.
1. Create an input to Battery Power by navigating to MAIN MENU | SETUP | SETUP I/O | SETUP
INPUT.
2. Enter a car call to any landing away from the FEO main recall landing by navigating to MAIN MENU
| DEBUG |ENTER CAR CALLS.
3. Set Hoistway Smoke to Main by navigating to MAIN MENU | SETUP | FIRE | HOISTWAY SMOKE |
MAIN or ALT.
4. Remove power.
5. Set Smoke HA to OFF.
6. The car moves to fire recall floor.
7. Press DOB and car doors open.
8. Restore power.
9. Verify car calls and hall calls.

10.1.3 FEO Phase II and Battery Lowering Device

Applicable Code – A17.1/B44-19 section 2.27.3.3.1(l)
2023 © Smartrise Engineering,
Inc.
All Rights Reserved
14

Advertisement

Table of Contents