Ac Wiring Of M100A_283 / M110A_283 - Delta M100A-280 Operation And Installation Manual

Grid-tie transformerless solar inverter
Hide thumbs Also See for M100A-280:
Table of Contents

Advertisement

3.4.7 AC Wiring of M100A_283 / M110A_283

- Always no energy on the AC power cables during the cable installation to
prevent electrical hazard.
M100A_283 / M110A_283
N
L2
AC entry - 28.9 mm
trade size gland
Figure 3-16: Location for AC terminal of M100A_283 / M110A_283
(1) Ensure the AC disconnect device is in "OFF"
(2) Strip off the insulation of each cable by 30mm.
(3) For the aluminum conductor, remove the oxide film of the conductor surface
and apply the protective grease.
(4) Pass the cable of L1, L2, L3 or neutral (if required) through each M40 cable
gland with the proper inner rubber.
(5) Follow the label to Connect L1, L2, L3 and neutral (if required).
(6) Tighten all screws of the terminal with 42.4 N-m torque.
(7) Fasten all AC cable glands for sealing.
M40
Table 3-6: Specification of M100A_283 / M110A_283 AC gland
M40
Cable diameter range
D1
21.7-28.9 mm
D2
16.2-21.7 mm
D3
12.0-16.2 mm
DANGER : ELECTRICAL HAZARD!!
L3
L1
D1
D2
After inserting conductor, torque
terminal nut by 42.4 N • m
D3
Torque
5.5-10
N • m
6.0
N • m
4.0-6.5
N • m
35
Installation
N
L3
L2
L1
P
Dimension of P
1.0-8.0 mm
1.0-6.5 mm
1.0-7.5 mm