7 Technical Information - Delta M100A-280 Operation And Installation Manual

Grid-tie transformerless solar inverter
Hide thumbs Also See for M100A-280:
Table of Contents

Advertisement

Technical Information
7 Technical Information
Model
Occasionally Max. voltage
Operating Voltage Range
MPP Voltage Range (Full Power)
Start Voltage
Rated Voltage
Max. Operating Current
Max. Short Current Capability (Isc)
Number of MPP Trackers
DC Connection Type
Surge Protection
Arc Fault Detection
Max. Apparent Power
Max. Actual Power
Rated Output Power
Max. Output Current
Rated Voltage
AC Voltage Range
Night Time Reactive Power
Operating Frequency Range
Power Factor (Adjustable)
Surge Protection
T.H.D
AC Connection Type
Night Time Consumption *
*
1 Maximum Withstand is 1100Vdc. However, the inverter will stop operating when the PV voltage is above 1000Vdc.
*
2 Ambient < 25°C: 470~860V ; Ambient < 30°C: 470~860V ; Ambient < 40°C: 520~580V
*3 Ambient Temperature < 33°C
*4 With RS-485 communication
Table 7-1A: Specifications
M100A_280 / M100A_283
DC Input
Type II SPD (built-in) ; Type I+II SPD (optional)
AC Output
100 kW @ 50°C ; 110 kW @ 40°C (480 V)
100 kW @ 40°C ; 110 kW @ 35°C (400 V)
100 kW @ 35°C ; 110 kW @ 25°C (380 V)
168 A for 380V / 400V / 440V ; 133 A for 480V
380V / 400V / 440V / 480V, 3Ø3W or 3Ø4W
Terminal block, Max. 240 mm² Cu and Al conductor
4
74
1000 V *
200 - 1000 V
520 - 840 V *
> 250 V
610 V
30 A / MPPT
50 A / MPPT
8
Amphenol H4 DC Connector
Built-in
110 kVA *
110 kW
80% - 120% of nominal AC voltage
66 kVAR
50 / 60Hz ± 5Hz
0.8 ind - 0.8 cap
Type II SPD
< 3% at Rated output current
< 3.5 W
M110A_283
1
2
3

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

M100a-283M110a-283