NATURAL GAS IGNITION AND REGULATION

• Bleed out the air contained in the gas piping, with due precautions
and with doors and windows open.
• Open the union on the pipe near the burner and then open slightly
the gas shut-off cocks.
When the characteristic odour of gas can be smelled, close the cut-off
cock.
• Wait the time necessary for the gas in the room to disperse outside.
Re-connect the burner to the gas pipeline.
• Check that there is water in the boiler and that the gate valves of the
system are open.
• Make sure that the combustion products may be freely vented throu-
gh the boiler and flue dampers.
• Make sure that the mains voltage corresponds to the manufacturer's
requirements and that all electrical connections made at the instal-
lation site are effected properly as illustrated in our wiring diagram.
• Make sure that the combustion head is long enough to enter the
furnace following the measure specified by the boiler manufacturer.
• Check that the air regulation device on the combustion head is in the
correct position to deliver the required fuel.
• The air passage between disk and combustion head must be consi-
derably reduced with minimum fuel delivery.
• Increase combustion air flow when fuel delivery increases.
• Refer to chapter "Air adjustment on the combustion head".
• Fit a pressure gauge of appropriate scale to the pressure intake on
the gas pressure switch (if the amount of pressure to be used allows
it, we recommend to use a water column instrument; do not use
instruments with indicator hands for low pressures).
10
2
1
ON / OFF main switch
2
Thermostatic line switch
3
Display
4
Unlock or RESET button
5
Fusibile.
9
Fuel loading button
10 Fuel selector switch
11 Programming keyboard
27 / 52
0006160032_202011
3
11
5
1
4
9
ENGLISH