SW3(SW-1)
ON
Obtain network address automatically
1
OFF
Obtain network address manually
ON
Revocation indoor unit network address
2
OFF
/

6. TEST RUNNING

Operate according to "gist for test running" on the electric control box
cover.
CAUTION
Test running can not start until the outdoor unit has been
connected to the power for 12hr.
Test running can not start until all the valves are affirmed
open.
Never make the forced running. (Or the protector sits back,
danger will occur.)
7. PRECAUTIONS ON REFRIGERANT
LEAKAGE
This air conditioner(A/C) adopts inncouous and nonflammable
refrigerant. The locating room of the A/C should big engough
that any refrigerant leakage is unable to reach critical thickness.
So certain esssential action can be taken on time.
Critical thickness------the Max. thickness of Freon without any
harm to person.
Refrigerant critical thickness: 0.44[kg/m ] for R410A.
Confirm the critical thickness through follow steps, and take
necessary actions.
1. Calculate the sum of the charge volume (A[kg]) Total
Refrigerant volume of 10HP=factory refrigerant
volume + superaddition
2. Calculate the indoor cubage (B[m ]) (as the minimum
cubage.
3. Calculate the refrigerant thickness
A[kg]
≤ critical thickness
3
B[m ]
Counter measure against over high thickness
1. Installmechanicalventilator to reduce the refrigerant thickness
under critical level. (ventilate regularly)
2. Install leak alarm facility related to mechanical ventilator if
you can not regularly ventilate.
Table 5-3
3
3
14
Outdoor unit
Indoor unit
Room full of leak refrigerant
(All refrigerant has run up)
b. Leak alarm related to mechanical ventilator
Indoor unit
(Leak hunting siren should be installed in
places easily keep refrigerant)
NOTE
Please press "constraint cool" button to carry out refrigerant
recycling process. Keep the low pressure above 0.2MPa, other
wise compressor may be burnt out.
7.1 Important information for the used
refrigerant
This product has the fluorinated gas, it is forbidden to release to air.
Refrigerant type: R410A; Volume of GWP: 2088;
GWP=Global Warming Potential
Factory charge
Model
Refrigerant/kg
2.95
8kW
2.95
10.5kW
3.30
12kW
3.90
14kW
16kW
3.90
18kW
4.50
Attention:
Frequency of Refrigerant Leak Checks
1) For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes of CO
50 tonnes of CO
equipment,at least every 12 months, or where
2
a leakage detection system is installed, at least every 24 months.
2) For equipment that contains fluorinated greenhouse gases in
quantities of 50 tonnes of CO
500 tonnes of CO
equipment,at least every six months, or where
2
a leakage detection system is installed, at least every 12 months.
3) For equipment that contains fluorinated greenhouse gases in
quantities of 500 tonnes of CO
three months, or where a leakage detection system is installed,
at least every six months.
4) Non-hermetically sealed equipment charged with fluorinated
greenhouse gases shall only be sold to the end user where evidence
is provide that the installation is to be carried out by an undertaking
certified person.
5) Only certificated person is allowed to do installation, operation
and maintenance.

8. TURN OVER TO CUSTOMER

The owner's manual of indoor unit and owner's manual of
outdoor or unit must be turned over to the customer. Explain
the contents in the owner's manual to the customers in details.
A. Ventilation
peristome
Fig. 7-1
tonnes CO
equivalent
2
6.16
6.16
6.89
8.14
8.14
9.40
equivalent or more,but of less than
2
equivalent or more,but of less than
2
equivalent or more,at least every
2