YASKAWA 1000 Series Installation Manual page 52

Ac drive lcd operator
Hide thumbs Also See for 1000 Series:

Advertisement

7 Related Parameters
No.
Name
Frequency
b1-01
Reference
Selection 1
Run
b1-02
Command
Selection 1
Frequency
b1-15
Reference 2
Run
b1-16
Command
Source 2
Voltage
b1-18
Reference
Source
LOCAL/
REMOTE
o2-01
Key
Function
Selection
52
Unit
A1000/
D1000 R1000
V1000
YES
N/A
N/A
YES
YES
YES
YES
N/A
N/A
YES
N/A
N/A
N/A
YES
N/A
YES
YES
N/A
YASKAWA ELECTRIC TOBP C730600 29G 1000-Series Option JVOP-180 Installation Manual
Description
Selects the source of the frequency reference.
0: Operator -Digital preset speed d1-01 to d1-
17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial
communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the Run command input source.
0: Operator -RUN and STOP keys on the LCD
Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial
communications
3: Option PCB
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial
communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the Run command input source.
0: Operator - RUN and STOP keys on the LCD
Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial
communications
3: Option PCB
Sets the input source for the DC bus voltage
reference.
0: LED operator or LCD operator
1: Control circuit terminal (analog input)
2: MEMOBUS/Modbus communications
3: Option card
7: Input voltage based control 1
8: Input voltage based control 2
Enables/Disables the option LOCAL/
REMOTE key.
0: Disabled
1: Enabled
Values
Default: 1
Range: 0 to 4
Default: 1
Range: 0 to 3
Default: 0
Range: 0 to 4
Default: 0
Range: 0 to 3
Default: 0
Range: 0 to 3,
7, 8
Default: 1
Range: 0, 1