Activating The Fast Stop Function; Updating The Firmware - SMA SUNNY TRIPOWER CORE2 Operating Manual

Hide thumbs Also See for SUNNY TRIPOWER CORE2:
Table of Contents

Advertisement

10 Operation
Procedure:
1. Select [Communication] in the menu.
2. Select [MODBUS].
3. Switching the communication on and off via Modbus.
Also see:
• Modbus ⇒ page 22

10.13 Activating the Fast Stop Function

After the installation, the fast stop function must be activated via the user interface of the inverter.
The following procedure must be carried out for each individual inverter.
Requirements:
☐ The contact for the fast stop is connected to digital input (see Section 8.7.3, page 49).
☐ You are logged in on the user interface as Service provider (see Section 10.2.2, page 57).
Procedure:
1. In parameter group Extended Model 2-1 set the parameter DIEmShutd to On.
2. If a fast stop is to be triggered when the contact is open: Set the parameter FsDIConfig in the
parameter group Extended Model 2-1 to On.
3. If a fast stop is to be triggered when the contact is closed: Set the parameter FsDIConfig in
the parameter group Extended Model 2-1 to Off.
Also see:
• Fast stop function ⇒ page 23

10.14 Updating the Firmware

It is not possible to set an automatic update for the inverter via the SMA Data Manager. Update
the firmware as follows with the existing update file via the user interface of the inverter.
Requirements:
☐ Ensure that AC and DC voltage is present at the inverter.
☐ An update file with the desired firmware of the product must be available. You can download
the update file from the product page under www.SMA-Solar.com.
☐ The firmware file was not unzipped even if the file ends with .zip..
☐ You are logged in on the user interface as Installer (see Section 10.2.1, page 56).
Procedure:
1. Select [Device] in the menu.
2. Select [Firmware update].
64
STP110-60-BE-en-16
SMA Solar Technology AG
Operating manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Stp 110-60

Table of Contents