16 Technical Data
MPP Voltage Range for rated power
Rated input voltage
Minimum input voltage
Initial input voltage
Maximum usable input current per input with an
input voltage < 600 V
Maximum usable input current per input with an
input voltage > 600 V
Maximum short-circuit current per input
Maximum reverse current into the PV array
Number of independent MPP inputs
Strings per MPP input
Overvoltage category as per IEC 62109-1

16.3 AC Output

Rated power at nominal AC voltage, 50 Hz
Maximum apparent power at cos φ = 1
Rated apparent power at cos φ = 1
Nominal grid voltage
Rated grid voltage
4)
Voltage range
Rated current at nominal grid voltage
Maximum output current
Maximum residual output current
Duration of the maximum residual output current
Total harmonic distortion
Inrush current
Rated grid frequency
4)
Grid frequency
Operating range at grid frequency 50 Hz
2)
In accordance with IEC 62109-2: I
3)
The topology prevents a reverse current from the inverter in the system
4)
Depending on the configured country data set
104
STP110-60-BE-en-16
2)
3)
< 10% of the nominal AC current for a
SC PV
SMA Solar Technology AG
500 V to 800 V
585 V
200 V
250 V
22 A
26 A
40 A
0 A
12
2
II
110000 W
110000 VA
110000 VA
400 V
400 V
320 V to 460 V
158.8 A
158.8 A
420 A
1 ms
< 3 %
maximum of 10 ms
50 Hz
50 Hz / 60 Hz
45 Hz to 55 Hz